CABINET CAPACITY | X90-5S UPS: power modules | Up to 350kW (5 x 70kW) or up to 250kVA (5 x 50kW) |
| X90-2S UPS: battery modules | 4, 8, 12, 16 or 20 battery modules |
| X90-BC: battery modules | Up to 36 additional battery modules |
INPUT | Voltage / frequency nominal | 480VAC (3W), 50/60Hz auto-sensing |
| Voltage / frequency range | 329 – 520VAC (L-L), 40–70Hz |
OUTPUT | Voltage | 480VAC (4W) |
| Frequency | 40–70Hz |
| Efficiency | Up to 96% online mode or 99% ECO mode |
| Overload capacity | 1105%-110% for 60min; 110%-125% for 10min; 126%-150% for 1min; >150% for 200ms |
BATTERY SYSTEM | Nominal voltage | +/-240VDC |
Charge Current (programmable) | 18A | 36A | 54A | 72A | 90A |
Dimensions & WEIGHTS | UPS & Battery Cabinet (W x D x H) | 31.5 x 42 x 79 in 787 lbs (UPS) / 23.6 x 42 x 79 in 838 lbs (BC) |
| Bypass enclosure (W x D x H) | 11.8 x 42 x 79 in / 400 lbs |
| Power & Battery module (W x D x H) | 17.2 x 31.2 x 5.25 in / 104 lbs (PM) 17.2 x 31.2 x 5.25 in / 73 lbs (BM) |
ENVIRONMENT | Operating temperature | 0–40°C (32–104°F) |
| Audible noise | < 69dBA at 1m |
| Altitude | 5,200 ft above sea level* |
APPROVALS | | UL-1778, cUL, FCC A, RoHS, TAA |
WARRANTY | | 2 years (USA and Canada) |
COMMUNICATIONS INTERFACE | | RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus) |
INCLUDED IN BOX | | User manual, RS-232 communication cable, USB cable |
AVAILABLE OPTIONS | | External Maintenance bypass, Battery Temperature Sensor |