The M90U is a scalable modular online double conversion UPS that protects critical data and equipment from power problems while supplying clean and reliable network grade power.

M90U can be configured with a fully redundant power module and battery modules. Should one module fail, the remaining modules smoothly take over the load. The power modules are independent and can be hot swapped without risk to the critical load.

Product Snapshot

  • Six capacities: 15kW, 20kW, 30kW, 40kW, 45kW, 60kW
  • Modular for capacity or redundancy
  • Hot swappable power modules
  • Up to 98% ECO mode or 94% online efficiency
  • Remote control and monitoring options
  • 2 year electronics, 2 year battery warranty (USA and Canada)

To receive a quote on M90U Modular Online Three Phase UPS contact a sales representative at sales@xpcc.com

    Get In touch

    What is 5 + 3 ?


    Specification

    MODEL NUMBERM90U-15M90U-20M90U-30M90U-40M90U-45M90U-60
    INPUTCapacity15kVA (15kW)20kVA (20kW)30kVA (30kW)40kVA (40kW)45kVA (45kW)60kVA (6kW)
     Nominal208/120V 50/60Hz auto sensing
     Range121-253VAC*(L-L) 40-70Hz
    OUTPUTVoltage208/120VAC
     Frequency50/60 ± 0.05Hz
     THD (full load)0.9
     Voltage regulation<2%
     Efficiency98% ECO mode, ≥ 94% online mode
     Overload capacity105%-110% for 60 min;110%-125% for 10min; 126%-150% for 1min; <150% for 200ms
    BATTERY SYSTEMNominal voltage±120V
     Temperature compensationYes with optional sensor
     Charging current (programable)8A16A24A8A16A24A
    PHYSICALEnclosure20.3″W x 39.4″D x 54″H/484 lbs
     Power module19.0”W x 28.0”D x 5.1”H / 74 lbs 
     Battery module4.1”W x 28.3”D x 6.0”H / 68 lbs
    ENVIRONMENTTemperature0–40°C (32–104°F)
     Altitude5,200 ft above sea level
     Audible noise< 65dBA at 1m 
    APPROVALS UL-1778 (TUV), cUL, FCC A, RoHS
    WARRANTY 2 years (USA and Canada)
    COMMUNICATIONS INTERFACE RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus)
    INCLUDED IN BOX User manual, RS-232 cable, Ramp for unloading UPS enclosure
    AVAILABLE OPTIONS External maintenance bypass, 480V input transformer, output distribution, battery temperature sensor

    *Depending on load level **Battery life is reduced above 30°C, UPS capacity derates above 30°C and 5,200 ft above sea level

    Documentation

    Copyright @ Applied Power Group. Designed By Digital Guider