INPUT | Capacity | 15kVA (15kW) | 20kVA (20kW) | 30kVA (30kW) | 40kVA (40kW) | 45kVA (45kW) | 60kVA (6kW) |
| Nominal | 208/120V 50/60Hz auto sensing |
| Range | 121-253VAC*(L-L) 40-70Hz |
OUTPUT | Voltage | 208/120VAC |
| Frequency | 50/60 ± 0.05Hz |
| THD (full load) | 0.9 |
| Voltage regulation | <2% |
| Efficiency | 98% ECO mode, ≥ 94% online mode |
| Overload capacity | 105%-110% for 60 min;110%-125% for 10min; 126%-150% for 1min; <150% for 200ms |
BATTERY SYSTEM | Nominal voltage | ±120V |
| Temperature compensation | Yes with optional sensor |
| Charging current (programable) | 8A | 16A | 24A | 8A | 16A | 24A |
PHYSICAL | Enclosure | 20.3″W x 39.4″D x 54″H/484 lbs |
| Power module | 19.0”W x 28.0”D x 5.1”H / 74 lbs |
| Battery module | 4.1”W x 28.3”D x 6.0”H / 68 lbs |
ENVIRONMENT | Temperature | 0–40°C (32–104°F) |
| Altitude | 5,200 ft above sea level |
| Audible noise | < 65dBA at 1m |
APPROVALS | | UL-1778 (TUV), cUL, FCC A, RoHS |
WARRANTY | | 2 years (USA and Canada) |
COMMUNICATIONS INTERFACE | | RS-232, EPO, intelligent slot for optional cards (Web/SNMP, Relay, Modbus) |
INCLUDED IN BOX | | User manual, RS-232 cable, Ramp for unloading UPS enclosure |
AVAILABLE OPTIONS | | External maintenance bypass, 480V input transformer, output distribution, battery temperature sensor |